Line 218: Line 218:
 Re-charge the battery or reduce the AC loads to continue operation. Re-charge the battery or reduce the AC loads to continue operation.
  
-If the error immediately pops up when switching on the inverter (without load) on a full battery the cause is most likely a broken internal fuse.+If the error immediately pops up when switching on the inverter (without load) on a full battery the cause is most likely a broken replaceable internal fuse. Contact your Victron dealer for support
 ==== Err 55, Err 56, Err 58 - Inverter self test failed ==== ==== Err 55, Err 56, Err 58 - Inverter self test failed ====
 The inverter performs diagnostic tests before it activates its output. In the case that one of these tests fails an error message is displayed and the inverter does not turn on. The inverter performs diagnostic tests before it activates its output. In the case that one of these tests fails an error message is displayed and the inverter does not turn on.
Line 229: Line 229:
 This error will not auto-reset. Check the installation and restart the unit using the power-switch. This error will not auto-reset. Check the installation and restart the unit using the power-switch.
  
 +==== Err 59 - ACIN1 relay test fault ====
 +
 +Automatic checking of the disconnect means failure.
 +This usually indicates a broken relay (sticky contact) in the AC input stage.
  
 ==== Information 65 - Communication warning ==== ==== Information 65 - Communication warning ====
Line 282: Line 286:
 Applies to Inverter RS models. Firmware versions 1.11 and higher. Applies to Inverter RS models. Firmware versions 1.11 and higher.
  
-The Inverter RS model used cannot be paired with a Multi RS and/or Transfer Switch+Inverter RS units cannot be paired with a Multi RS and/or Transfer Switch.
-Only Inverter RS models with a production code newer than HQYYWW can be used for this purpose. +
-Only the incompatible Inverter RS units will remain off.+
  
 ==== Err 71 - Network misconfigured ==== ==== Err 71 - Network misconfigured ====
Line 310: Line 312:
  
 The number of inverters in parallel doesn't match with the transfer capabilities of the ac input relay of the Multi RS or Transfer switch. The number of inverters in parallel doesn't match with the transfer capabilities of the ac input relay of the Multi RS or Transfer switch.
 +Firmware v1.12 does not support parallel units and a grid connection, so any combination of a Multi RS with a grid connection with more than one unit in parallel will trigger this error code on the Multi RS. The Multi RS only supports 3 units in 3-phase configuration at the moment.
  
 The inverters remain operational, they won't connect to the grid. Once the issue is resolved the units will connect. The inverters remain operational, they won't connect to the grid. Once the issue is resolved the units will connect.